An exposure of sensitive information vulnerability exists in the Rockwell Automation FactoryTalk® System Service.

LOW 1.8EPSS 0.18%

Does this matter?

Lower severity and a low EPSS score (0.18%). Track it; it rarely justifies an emergency change on its own.

Description

An exposure of sensitive information vulnerability exists in the Rockwell Automation FactoryTalk® System Service. A malicious user could exploit this vulnerability by starting a back-up or restore process, which temporarily exposes private keys, passwords, pre-shared keys, and database folders when they are temporarily copied to an interim folder. This vulnerability is due to the lack of explicit permissions set on the backup folder. If private keys are obtained by a malicious user, they could impersonate resources on the secured network.

CVSS 4.0
1.8 LOWCVSS:4.0/AV:L/AC:L/AT:P/PR:L/UI:A/VC:N/VI:N/VA:N/SC:H/SI:N/SA:N/E:X/CR:X/IR:X/AR:X/MAV:X/MAC:X/MAT:X/MPR:X/MUI:X/MVC:X/M
EPSS
0.18% probability · 7th percentile
CISA KEV
Not listed
Weakness
CWE-269, CWE-276
Affected
rockwellautomation/factorytalk policy manager · rockwellautomation/factorytalk system services
Source
PSIRT@rockwellautomation.com

Source: NVD record, EPSS from FIRST.org, KEV from CISA. Refreshed daily.