CVE-2024-50954

The XINJE XL5E-16T and XD5E-24R-E programmable logic controllers V3.5.3b-V3.7.2a have a vulnerability in handling Modbus messages.

HIGH 7.5EPSS 0.43%

Does this matter?

High impact if exploited, but EPSS currently rates exploitation as unlikely (0.43%). Schedule it in the normal patch cycle and watch for a rise in EPSS or a public exploit.

Description

The XINJE XL5E-16T and XD5E-24R-E programmable logic controllers V3.5.3b-V3.7.2a have a vulnerability in handling Modbus messages. When a TCP connection is established with the above series of controllers within a local area network (LAN), sending a specific Modbus message to the controller can cause the PLC to crash, interrupting the normal operation of the programs running in the PLC. This results in the ERR indicator light turning on and the RUN indicator light turning off.

CVSS 3.1
7.5 HIGHCVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H
EPSS
0.43% probability · 36th percentile
CISA KEV
Not listed
Weakness
CWE-703