CVE-2022-43110
Voltronic Power ViewPower through 1.04-21353 and PowerShield Netguard before 1.04-23292 allows a remote attacker to configure the system via an unspecified web interface.
Does this matter?
High impact if exploited, but EPSS currently rates exploitation as unlikely (0.66%). Schedule it in the normal patch cycle and watch for a rise in EPSS or a public exploit.
Description
Voltronic Power ViewPower through 1.04-21353 and PowerShield Netguard before 1.04-23292 allows a remote attacker to configure the system via an unspecified web interface. An unauthenticated remote attacker can make changes to the system including: changing the web interface admin password, view/change system configuration, enumerate connected UPS devices and shut down connected UPS devices. This extends to being able to configure operating system commands that should run if the system detects a connected UPS shutting down.
- CVSS 3.1
- 9.8 CRITICALCVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H
- EPSS
- 0.66% probability · 50th percentile
- CISA KEV
- Not listed
- Weakness
- CWE-284, CWE-306, CWE-425
- Source
- cve@mitre.org
References
Source: NVD record, EPSS from FIRST.org, KEV from CISA. Refreshed daily.