SOC status:Duty analyst on shift

UK Cyber Defence
VulnerabilityModified

CVE-2021-41545

A vulnerability has been identified in Desigo DXR2 (All versions < V01.21.142.5-22), Desigo PXC3 (All versions < V01.21.142.4-18), Desigo PXC4 (All versions < V02.20.142.10-10884), Desigo PXC5 (All versions < V02.20.142.10-10884).

HIGH 7.5EPSS 0.92%

Does this matter?

High impact if exploited, but EPSS currently rates exploitation as unlikely (0.92%). Schedule it in the normal patch cycle and watch for a rise in EPSS or a public exploit.

Description

A vulnerability has been identified in Desigo DXR2 (All versions < V01.21.142.5-22), Desigo PXC3 (All versions < V01.21.142.4-18), Desigo PXC4 (All versions < V02.20.142.10-10884), Desigo PXC5 (All versions < V02.20.142.10-10884). When the controller receives a specific BACnet protocol packet, an exception causes the BACnet communication function to go into a “out of work” state and could result in the controller going into a “factory reset” state.

CVSS 3.1
7.5 HIGHCVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H
EPSS
0.92% probability · 58th percentile
CISA KEV
Not listed
Weakness
CWE-248
Affected
siemens/desigo dxr2 firmware · siemens/desigo pxc3 firmware · siemens/desigo pxc4 firmware · siemens/desigo pxc5 firmware
Source
productcert@siemens.com