SOC status:Duty analyst on shift

UK Cyber Defence
VulnerabilityModified

CVE-2021-35533

Improper Input Validation vulnerability in the APDU parser in the Bidirectional Communication Interface (BCI) IEC 60870-5-104 function of Hitachi Energy RTU500 series allows an attacker to cause the receiving RTU500 CMU of which the BCI is enabled to…

HIGH 7.5EPSS 0.92%

Does this matter?

High impact if exploited, but EPSS currently rates exploitation as unlikely (0.92%). Schedule it in the normal patch cycle and watch for a rise in EPSS or a public exploit.

Description

Improper Input Validation vulnerability in the APDU parser in the Bidirectional Communication Interface (BCI) IEC 60870-5-104 function of Hitachi Energy RTU500 series allows an attacker to cause the receiving RTU500 CMU of which the BCI is enabled to reboot when receiving a specially crafted message. By default, BCI IEC 60870-5-104 function is disabled (not configured). This issue affects: Hitachi Energy RTU500 series CMU Firmware version 12.0.* (all versions); CMU Firmware version 12.2.* (all versions); CMU Firmware version 12.4.* (all versions).

CVSS 3.1
7.5 HIGHCVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H
EPSS
0.92% probability · 58th percentile
CISA KEV
Not listed
Weakness
CWE-20
Affected
hitachienergy/rtu500 firmware
Source
cybersecurity@hitachienergy.com

Source: NVD record, EPSS from FIRST.org, KEV from CISA. Refreshed daily.