SOC status:Duty analyst on shift

UK Cyber Defence
VulnerabilityModified

CVE-2020-27738

A vulnerability has been identified in APOGEE PXC Compact (BACnet) (All versions < V3.5.5), APOGEE PXC Compact (P2 Ethernet) (All versions < V2.8.20), APOGEE PXC Modular (BACnet) (All versions < V3.5.5), APOGEE PXC Modular (P2 Ethernet) (All versions <…

HIGH 7.4EPSS 3.66%

Does this matter?

High impact if exploited, but EPSS currently rates exploitation as unlikely (3.66%). Schedule it in the normal patch cycle and watch for a rise in EPSS or a public exploit.

Description

A vulnerability has been identified in APOGEE PXC Compact (BACnet) (All versions < V3.5.5), APOGEE PXC Compact (P2 Ethernet) (All versions < V2.8.20), APOGEE PXC Modular (BACnet) (All versions < V3.5.5), APOGEE PXC Modular (P2 Ethernet) (All versions < V2.8.20), Nucleus NET (All versions), Nucleus ReadyStart V3 (All versions < V2017.02.3), Nucleus ReadyStart V4 (All versions < V4.1.0), Nucleus Source Code (Versions including affected DNS modules), SIMOTICS CONNECT 400 (All versions < V0.5.0.0), TALON TC Compact (BACnet) (All versions < V3.5.5), TALON TC Modular (BACnet) (All versions < V3.5.5). The DNS domain name record decompression functionality does not properly validate the pointer offset values. The parsing of malformed responses could result in a read access past the end of an allocated structure. An attacker with a privileged position in the network could leverage this vulnerability to cause a denial-of-service condition.

CVSS 3.1
7.4 HIGHCVSS:3.1/AV:N/AC:H/PR:N/UI:N/S:U/C:H/I:N/A:H
EPSS
3.66% probability · 89th percentile
CISA KEV
Not listed
Weakness
CWE-788, CWE-119
Affected
siemens/simotics connect 400 firmware · siemens/nucleus net · siemens/nucleus readystart v3 · siemens/nucleus readystart v4 · siemens/nucleus source code
Source
productcert@siemens.com

Source: NVD record, EPSS from FIRST.org, KEV from CISA. Refreshed daily.