SOC status:Duty analyst on shift

UK Cyber Defence
VulnerabilityModified

CVE-2020-15782

A vulnerability has been identified in SIMATIC Drive Controller family (All versions < V2.9.2), SIMATIC ET 200SP Open Controller CPU 1515SP PC (incl.

CRITICAL 9.8EPSS 5.18%

Does this matter?

High impact if exploited, but EPSS currently rates exploitation as unlikely (5.18%). Schedule it in the normal patch cycle and watch for a rise in EPSS or a public exploit.

Description

A vulnerability has been identified in SIMATIC Drive Controller family (All versions < V2.9.2), SIMATIC ET 200SP Open Controller CPU 1515SP PC (incl. SIPLUS variants) (All versions), SIMATIC ET 200SP Open Controller CPU 1515SP PC2 (incl. SIPLUS variants) (All versions < V21.9), SIMATIC S7-1200 CPU family (incl. SIPLUS variants) (All versions < V4.5.0), SIMATIC S7-1500 CPU family (incl. related ET200 CPUs and SIPLUS variants) (All versions < V2.9.2), SIMATIC S7-1500 Software Controller (All versions < V21.9), SIMATIC S7-PLCSIM Advanced (All versions < V4.0), SINAMICS PERFECT HARMONY GH180 Drives (Drives manufactured before 2021-08-13), SINUMERIK MC (All versions < V6.15), SINUMERIK ONE (All versions < V6.15). Affected devices are vulnerable to a memory protection bypass through a specific operation. A remote unauthenticated attacker with network access to port 102/tcp could potentially write arbitrary data and code to protected memory areas or read sensitive data to launch further attacks.

CVSS 3.1
9.8 CRITICALCVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H
EPSS
5.18% probability · 92th percentile
CISA KEV
Not listed
Weakness
CWE-119
Affected
siemens/simatic driver controller firmware · siemens/s7-1200 cpu firmware · siemens/s7-1500 cpu firmware · siemens/simatic s7-1500 software controller · siemens/simatic s7-plcsim advanced · siemens/et 200sp open controller firmware
Source
productcert@siemens.com

Source: NVD record, EPSS from FIRST.org, KEV from CISA. Refreshed daily.