CVE-2020-12005
FactoryTalk Linx versions 6.00, 6.10, and 6.11, RSLinx Classic v4.11.00 and prior,Connected Components Workbench: Version 12 and prior, ControlFLASH: Version 14 and later, ControlFLASH Plus: Version 1 and later, FactoryTalk Asset Centre: Version 9 and…
Does this matter?
High impact if exploited, but EPSS currently rates exploitation as unlikely (1.84%). Schedule it in the normal patch cycle and watch for a rise in EPSS or a public exploit.
Description
FactoryTalk Linx versions 6.00, 6.10, and 6.11, RSLinx Classic v4.11.00 and prior,Connected Components Workbench: Version 12 and prior, ControlFLASH: Version 14 and later, ControlFLASH Plus: Version 1 and later, FactoryTalk Asset Centre: Version 9 and later, FactoryTalk Linx CommDTM: Version 1 and later, Studio 5000 Launcher: Version 31 and later Stud, 5000 Logix Designer software: Version 32 and prior is vulnerable. A vulnerability exists in the communication function that enables users to upload EDS files by FactoryTalk Linx. This may allow an attacker to upload a file with bad compression, consuming all the available CPU resources, leading to a denial-of-service condition.
- CVSS 3.1
- 7.5 HIGHCVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H
- EPSS
- 1.84% probability · 78th percentile
- CISA KEV
- Not listed
- Weakness
- CWE-434
- Affected
- rockwellautomation/factorytalk linx · rockwellautomation/rslinx classic
- Source
- ics-cert@hq.dhs.gov
References
- https://www.us-cert.gov/ics/advisories/icsa-20-163-02Third Party Advisory, US Government Resource
- https://www.us-cert.gov/ics/advisories/icsa-20-163-02Third Party Advisory, US Government Resource
Source: NVD record, EPSS from FIRST.org, KEV from CISA. Refreshed daily.