CVE-2019-19279
A vulnerability has been identified in SIPROTEC 4 and SIPROTEC Compact relays equipped with EN100 Ethernet communication modules (All versions).
Does this matter?
High impact if exploited, but EPSS currently rates exploitation as unlikely (1.59%). Schedule it in the normal patch cycle and watch for a rise in EPSS or a public exploit.
Description
A vulnerability has been identified in SIPROTEC 4 and SIPROTEC Compact relays equipped with EN100 Ethernet communication modules (All versions). Specially crafted packets sent to port 50000/UDP of the EN100 Ethernet communication modules could cause a Denial-of-Service of the affected device. A manual reboot is required to recover the service of the device. At the time of advisory publication no public exploitation of this security vulnerability was known to Siemens.
- CVSS 3.1
- 7.5 HIGHCVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H
- EPSS
- 1.59% probability · 75th percentile
- Public exploits
- None in Exploit-DB
- CISA KEV
- Not listed
- Weakness
- CWE-20
- Affected
- siemens/siprotec 4 · siemens/siprotec compact
- Source
- productcert@siemens.com
EPSS 1.6% since 26 October 2026; no change recorded yet. Points are recorded when the score first appears and whenever it moves by a percentage point or more.
References
Source: NVD record, EPSS from FIRST.org, KEV from CISA, exploits from Exploit-DB. Refreshed daily. Download this record as JSON.