CVE-2019-13553
The authentication mechanism on affected systems is configured using hard-coded credentials.
Does this matter?
High impact if exploited, but EPSS currently rates exploitation as unlikely (2.30%). Schedule it in the normal patch cycle and watch for a rise in EPSS or a public exploit.
Description
Rittal Chiller SK 3232-Series web interface as built upon Carel pCOWeb firmware A1.5.3 – B1.2.4. The authentication mechanism on affected systems is configured using hard-coded credentials. These credentials could allow attackers to influence the primary operations of the affected systems, namely turning the cooling unit on and off and setting the temperature set point.
- CVSS 3.1
- 9.8 CRITICALCVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H
- EPSS
- 2.30% probability · 82th percentile
- CISA KEV
- Not listed
- Weakness
- CWE-798
- Affected
- carel/pcoweb firmware
- Source
- ics-cert@hq.dhs.gov
References
- http://seclists.org/fulldisclosure/2019/Oct/45
- https://www.us-cert.gov/ics/advisories/icsa-19-297-01Third Party Advisory, US Government Resource
- http://seclists.org/fulldisclosure/2019/Oct/45
- https://www.us-cert.gov/ics/advisories/icsa-19-297-01Third Party Advisory, US Government Resource
Source: NVD record, EPSS from FIRST.org, KEV from CISA. Refreshed daily.