CVE-2017-9664

In ABB SREA-01 revisions A, B, C: application versions up to 3.31.5, and SREA-50 revision A: application versions up to 3.32.8, an attacker may access internal files of ABB SREA-01 and SREA-50 legacy remote monitoring tools without any authorization…

CRITICAL 9.8EPSS 2.62%

Does this matter?

High impact if exploited, but EPSS currently rates exploitation as unlikely (2.62%). Schedule it in the normal patch cycle and watch for a rise in EPSS or a public exploit.

Description

In ABB SREA-01 revisions A, B, C: application versions up to 3.31.5, and SREA-50 revision A: application versions up to 3.32.8, an attacker may access internal files of ABB SREA-01 and SREA-50 legacy remote monitoring tools without any authorization over the network using a HTTP request which refers to files using ../../ relative paths. Once the internal password file is retrieved, the password hash can be identified using a brute force attack. There is also an exploit allowing running of commands after authorization.

CVSS 3.0
9.8 CRITICALCVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H
EPSS
2.62% probability · 85th percentile
CISA KEV
Not listed
Weakness
CWE-23, CWE-22
Affected
abb/srea-50 firmware · abb/srea-01 firmware
Source
ics-cert@hq.dhs.gov

References