SOC status:Duty analyst on shift

UK Cyber Defence
VulnerabilityModified

CVE-2013-2807

By sending a datagram to the service over Port 4444/UDP with the “Record Data Size” field modified to a specifically oversized value, the service will calculate an undersized value for the “Total Record Size” that will cause an out-of-bounds read access…

HIGH 7.5EPSS 3.85%

Does this matter?

High impact if exploited, but EPSS currently rates exploitation as unlikely (3.85%). Schedule it in the normal patch cycle and watch for a rise in EPSS or a public exploit.

Description

Rockwell Automation RSLinx Enterprise Software (LogReceiver.exe) CPR9, CPR9-SR1, CPR9-SR2, CPR9-SR3, CPR9-SR4, CPR9-SR5, CPR9-SR5.1, and CPR9-SR6 does not handle input correctly and results in a logic error if it calculates an incorrect value for the “Total Record Size” field. By sending a datagram to the service over Port 4444/UDP with the “Record Data Size” field modified to a specifically oversized value, the service will calculate an undersized value for the “Total Record Size” that will cause an out-of-bounds read access violation that leads to a service crash. The service can be recovered with a manual reboot. The patches and details pertaining to these vulnerabilities can be found at the following Rockwell Automation Security Advisory link (login is required): https://rockwellautomation.custhelp.com/app/answers/detail/a_id/537599

CVSS 3.0
7.5 HIGHCVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H
EPSS
3.85% probability · 90th percentile
CISA KEV
Not listed
Weakness
CWE-190, CWE-125
Affected
rockwellautomation/rslinx enterprise
Source
ics-cert@hq.dhs.gov

References