CVE-2011-20002

A vulnerability has been identified in SIMATIC S7-1200 CPU V1 family (incl.

HIGH 8.3EPSS 0.30%

Does this matter?

High impact if exploited, but EPSS currently rates exploitation as unlikely (0.30%). Schedule it in the normal patch cycle and watch for a rise in EPSS or a public exploit.

Description

A vulnerability has been identified in SIMATIC S7-1200 CPU V1 family (incl. SIPLUS variants) (All versions < V2.0.2), SIMATIC S7-1200 CPU V2 family (incl. SIPLUS variants) (All versions < V2.0.2). Affected controllers are vulnerable to capture-replay in the communication with the engineering software. This could allow an on-path attacker between the engineering software and the controller to execute any previously recorded commands at a later time (e.g. set the controller to STOP), regardless whether or not the controller had a password configured.

CVSS 4.0
8.3 HIGHCVSS:4.0/AV:N/AC:L/AT:P/PR:N/UI:N/VC:N/VI:H/VA:H/SC:N/SI:N/SA:N/E:X/CR:X/IR:X/AR:X/MAV:X/MAC:X/MAT:X/MPR:X/MUI:X/MVC:X/M
EPSS
0.30% probability · 22th percentile
CISA KEV
Not listed
Weakness
CWE-294
Source
productcert@siemens.com