{"id":"CVE-2025-9042","url":"https://www.cyber-defence.io/tools/cve/CVE-2025-9042","generatedAt":"2026-10-28T05:26:14.411Z","title":"A security issue exists due to improper handling of CIP Class 32’s request when a module is inhibited on the 5094-IY8 device.","description":"A security issue exists due to improper handling of CIP Class 32’s request when a module is inhibited on the 5094-IY8 device. It causes the module to enter a fault state with the Module LED flashing red. Upon un-inhibiting, the module returns a connection fault (Code 16#0010), and the module cannot recover without a power cycle.","published":"2025-08-14T15:15:45.000Z","lastModified":"2026-06-17T10:08:13.000Z","status":"Deferred","sourceIdentifier":"PSIRT@rockwellautomation.com","cvss":{"version":"4.0","score":8.7,"severity":"HIGH","vector":"CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:N/VI:N/VA:H/SC:N/SI:N/SA:N/E:X/CR:X/IR:X/AR:X/MAV:X/MAC:X/MAT:X/MPR:X/MUI:X/MVC:X/M"},"cwe":["CWE-1287"],"affected":[],"epss":{"score":0.00322,"percentile":0.25051,"date":"2026-10-27","history":[]},"kev":{"listed":false},"exploits":{"count":0,"verified":false,"firstPublished":null,"source":"Exploit-DB (https://gitlab.com/exploit-database/exploitdb)","entries":[]},"verdict":{"level":"high","text":"High impact if exploited, but EPSS currently rates exploitation as unlikely (0.32%). Schedule it in the normal patch cycle and watch for a rise in EPSS or a public exploit."},"changes":[],"references":[{"url":"https://www.rockwellautomation.com/en-us/trust-center/security-advisories/advisory.SD1737.html","source":"PSIRT@rockwellautomation.com"}],"sources":{"nvd":"https://nvd.nist.gov/vuln/detail/CVE-2025-9042","epss":"https://www.first.org/epss/","kev":"https://www.cisa.gov/known-exploited-vulnerabilities-catalog","exploitdb":"https://www.exploit-db.com/"},"licence":"CC BY 4.0 — link back to the CVE Explorer if you publish the results; upstream data remains subject to its own terms."}